Illinois Reuse Machineries and Industrial Equipment Newsboad   >   Illinois   >   Aurora   >   Fenwal mfg.# 829-019 direct spark ignition control

Fenwal mfg.# 829-019 direct spark ignition control

Fenwal Mfg.# 829-019 Direct Spark Ignition Control
* Positive ignition/proof of flame
* Fail-safe on malfunction, spark interruption upon ignition
* Can be used on natural, manufactured or LP gas
* Up to three prepurge and trial for ignition periods before lockout
* Can be mounted vertically or horizontally
* Reset from lockout is accomplished by interrupting power to system
* Provides up to a 15-second delay before sparks are generated and valve is energized to permit main burner gas flow
* Input voltage: 24VAC, 50/60 Hz
* Valve relay contact rating: 0.6A
* Ambient temperature: -40 F to +150 F
* Flame failure response time: 0.8 seconds